Mô tả sản phẩm
Bộ Ghi Dữ Liệu - Recorder model PHU, EDS10-79b
Input system
Number of input points:
9, 18, 27 or 36 points (Can be selected at the time of purchase)
Input circuit: Input mutual isolation (See ”Others” on page 4 for the withstand voltage)
Resistance bulb measured current:
about. 1 mA
Measuring cycles:
9 or 18 points….100ms cycles
27 or 36 points….200ms cycles
Recording cycle: 1 second to 12 hours
Input types: Thermocouple, resistance bulb, DC voltage, and DC current (Shunt resistors are fitted in input terminals).
Note) Provide a shunt resistor (type: PHZP0101) separately.
Measuring range
Selection of input types:
By key operation on the front panel. Note that the same input type (thermocouple, resistance bulb, voltage) should be set ev-ery 2 channels. Refer to "Setting method of input types" for details.
Burn-out function:
Provided as standard for thermocouple and resistance bulb inputs. If the input has been open-circuited, the recording level swings over 100%.
Thermocouple burn-out current: approx. 0.2 µA
Input filter function:
Settable for each channel (primary delay filter)
Time constants are settable in the range from 0 to 900 sec.
Scaling function: Possible by DC voltage (current) input
Scaling range: -32767 to 32767
Decimal position:
settable at any point
Unit symbol: Selectable out of 125 different units or 12 user units of up to 7 characters.
Subtraction function:
Subtraction between each channel is allowed.
Totalizing function:
The measured value of each channel can be totalized. Applicable to daily, monthly, annual or external input totalizing.
F value calculation function:
F value (extinction value of bacteria by sterilization by heating) can be calculated from the measured temperature by each channel.
Square rooter function:
Square rooter can be performed against the input value per each channel.
Computation function:
The following calculation is available with the computation function.
(1) Computation function:
Addition, subtraction, multiplication, division, absolute value, exponential, square-root extraction, LOG, LN, EXP, humidity, maximum, minimum, aver-age, and integration.
(2) Computation input enable:
Analog input (Ch1 to 72), integration input (Ch1 to 72), DI (DI1 to 16), communication input (No.1 to 36), and constant number (No.1 to 60).
Indication system
Indicator: 12” TFT color LCD (800 x 600 dots) with backlight, no contrast adjustment.
On the LCD, certain picture elements remain lit or extinguished. On account of the nature inherent to LCD, the brightness may be non-uniform. But, such are not troubles.
Color of indication:
14 colors
Applicable language:
English, French (switchable)
Life of backlight: 50,000 hours in terms of total lighting time. (Replace the backlight as a set of display unit. If the LCD extinguishing function is resorted to, the LCD can be used longer as much.)
Trend display: Direction: vertical and horizontal
Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum).
Display refreshment cycles:select from 1 second to 12 hours. Scale display or no-display can be se-lected.
Bar graph display:
Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum).
Display refreshment cycles: 1 second
Analog meter display:
Number of channels: 10, 6 or 4 channels per screen group. Display in bar graphs or in analog meters can be selected.
Display refresh cycle: 1 second
Digital display: Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points
at the maximum).
Display refreshment cycles: 1 second
Totalizing data display:
Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum).
Display refresh cycle: 1 second
Event summary display:
Alarm summary and message summary can be displayed. The message occurrence information and message display can be switched.
Ethernet log display:
E-mail sending, FTP server log in/off and MODBUS TCP/IP communication start/stop can be displayed.
Parameter display/set:
Already-set Data Display and Set Change Display screen
TAG indication: Number of characters to be displayed:
Up to 8 characters
Up to 8 characters (Note 1) at 10 or 6 channel display.
Up to 16 characters at 4 channel dis-play.
Note 1: Up to 7 characters only can be
displayed on certain screens.
Characters to be displayed:
Alphanumerics
Tag, uni t and channel No. display:
Which can be displayed depends on the particular screen. Refer to the table below.
(Keywords only are extracted.)
Historical trend display:
Displays past recording data read from compact flash, currently recording data or just recorded data. The recording chart can be scrolled or, via time designation, the control can jump to an arbitrary recording chart.
Number of screen groups:
8 groups (Up to 10 channels per 1 group can be registered.)
Keyboard
No. of Keys: 8
Function: Use to select various screens and set
various parameters.
Recording function
External memory media:
Compact Flash card
Format according to FAT16 or FAT. Otherwise, reading and saving are impos-sible.
Recording capacity:
1 GB maximum (compact flash). Limiting the recording file to 64 MB is recom-mended (for 112 hours if display refresh cycle is 1 second. See Table 1 (p. 6).) If impossible, up to 256 MB is tolerated. A file recorded beyond could not be opened.
* Please change the compact flash every six month to prevent the data losing.
Recording method:
Turning ON the REC key allows measured data to be written at fixed cycles.
Recorded as a new file whenever the recording starts.
Data save cycles:
Linked to the display refreshment cycles on the ”Real Time Trend” screen. How-ever, they are automatically set to about 1 minute if the refreshment cycles are set to less than 1 minute.
Trend data: Measurement data sampled at measurement cycle is saved in terms of mean value, instantaneous value or maximum/minimum value.
Event data: Saves alarm data and message data.
Further saves power ON and OFF, if any, after starting recording.
Totalizing value data:
Total izing value data at designated timing is recorded per channel .
Totalized value data at designated totalized value recording cycle or the sum total is recorded in the totalizing file. You can choose which type you want to record.
For each cahnnel. it can be select as totalizing action from Analog input to-talization, Digital input count or period of Digital input ON, and it can be select as totalizing period type from Dairy, Weekly, Monthly, Annual , Periodic, Dairy (time set) or External input signal. Even if a power failure occues during totalization and then the power is restored,the totalization restarts from the value before power failure.
Configuration data:
Configuration data can be saved. And this data can also download to recorder.
Storage capacity :
Approximately 3 years when the display refresh cycle is 30 seconds (in case of 9-channel recording in ASCII data format, and 512 MB compact flash used). Refer to Table 1.
Residual capacity of memory:
Indicates how much of the memory card has been used on the screen. If the residual capacity is none, the recording stops.
Compact flash card form: PHZP1301-512
(CF card) (If a card other than the above is used, no operation assurance is ensured. Meanwhile, as for other CF cards for which operation check will have been completed, the results will be posted on our company's homepage sequentially. Please refer to this website.)
Data format: Either of ASCII or binary format can be selected. (Switching cannot be made while the recording is in progress. In the case of ASCII format, the data can be directly read on Excel, etc. The data recorded in binary format cannot be read directly.)
Approximately 166 bytes per sampling for maximum/minimum recording of 9-channel input in ASCII format, or approximately 40 bytes for maximum/minimum recording of 9-channel input in binary format.
Alarm function
No. of settings: Up to 4 alarms for each channel are set-
table.
Type of alarm: High/Low limits
Indication: Status (alarm types) is displayed on digital display unit when an alarm oc-curs.
Historical display on alarm summary (Alarm start/cancel time and alarm types)
Hysteresis: Set within the recording range of 0 to 100%
Acts on high or low limit alarm, and does not affect the battery alarm nor memory full alarm.
Relay output: Number of points; 20 (option: Up to 2 cards with relay output can be mounted.)
Transistor output (open collector output): 16 points (option)
Alarm latch function:
Holds alarm indication and alarm output even after measurement value has left the alarm range.
ON/OFF operation is performed according to key setting.
Power supply
Rated power voltage: 100 to 240V AC
Range of operating voltage: 90 to 264V AC
Supply frequency: 50/60Hz ±2% (both employable)
Power consumption
Power voltage |
Consumption |
100V AC |
About 65VA |
240V AC |
About 80VA |
Structure
Mounting method:
Panel-mounted (vertical panel)
Thickness of panel: 2 to 26 mm
Materials: Stainless steel for case, PC-ABS for bezel
Color: Silver for case, Munsell N2.0 (black) for bezel
External dimensions:
300 (W) × 300 (H) × 220.5 (D) mm
Mass: About 4.7 kg (9-point input, without option)
About 6.4 kg (full option)
External terminal board:
Input terminal: M3 screw terminal
Power terminal: M4 screw terminal
Operating condition
Power supply voltage:
90 to 264V AC
Power supply frequency:
50/60Hz ±2% (sharing)
Ambient temperature:
Without Ethernet function: 0 to 50°C*1
With Ethernet function: 0 to 40°C*2
Ambient humidity:
20 to 80%RH
Vibration: 10 to 60Hz 0.2m/s2
or less
Shock: None
Magnetic field: 400 A/m or less
Signal source resistance:
Thermocouple input .… 1kΩ or less
Resistance bulb input .… 10Ω/wire or less (resistance of each wire of 3-wire system should be balanced).
Voltage input .… 0.1% or less of input resistance
Mounting posture:
Forward tilt 0, backward tilt within 30,
horizontal 0
Warm-up time: One hour or more after power ON
*1: In case of the 12th digit of ordering code is ”Y”.
*2: In case of the 12th digit of ordering code is ”E”.
Reference standard
Accuracy/resolution:
Measuring conditions (23±2˚C, 65±10% RH, power voltage, frequency fluctuation within ±1%, no external noise, warm-up time of 1 hour or more, vertical mounting, standard values of signal source resistance and wiring resistance... within 1% )
Note 1) Digital indication accuracy is a percentage (%) with respect to
input range of 1 page.
Note 2) No error of reference contact compensation of thermocouple is
included.
Ni100
Cu50
0.1°C
Error of reference contact compensation:
K, E, J, T, N, L, U, PN: ±0.5˚C
R, S, B, W: ±1.0˚C
(when measured at 0˚C or more)
Max. input voltage:
Thermocouple, resistance bulb,
DC voltage: ±10V DC (continuous)
Input impedance: Thermocouple,
DC voltage: About 1MΩ
------------------------------------------------------------------------------------------------------------------------------------
ĐẠI LÝ PHÂN PHỐI CHÍNH THỨC TẠI VIỆT NAM | CÔNG TY TNHH TM-DV-KT CAO VIỆT CƯỜNG
Số 89 hẻm 249 Tân Kỳ Tân Quý, P.Tân Sơn Nhì, Q.Tân Phú, HCMC
Tel: 08-3813 4681/Fax: 08-3813 4680
Hotline: 0908 507 021/ 0909 951 237 | Email: sales@caovietcuong.com
Website: www.caovietcuong.com | www.thietbidomuc.com